Measuring transducer for temperature (Pt1000)
Measuring transducers of type VPT5 convert signals from a Pt1000 measuring element into standardised output signals. They are mounted on G rails or top-hat rails. The sensor input and supply voltage for the output signal are galvanically isolated. Its compact and robust design, as well as the relevant shipbuilding approvals, make this product ideal for marine applications.
Supply voltage Us | 9...32 VDC |
Input signal | Pt1000 two-wire sensors in accordance with EN60751 class B |
Output signal | VPx5..-I: 0 ... 20 mA (VPx5..-I1), 4 ... 20 mA (VPx5..-I2),load resistance 500 Ω max. |
Operating temperature | -20 °C ... +70 °C |
Connection | DIN EN 46244 gold-plated tab connector A6.3 x 0.8 |
Mounting | TS32 G-rail or TS35 top-hat rail |
Type code structure | |||
---|---|---|---|
VPT5 | 1 | -I2 | Example: VPT51-I2 |
Input signal | |||
| Output signal |
Type code VPT5 … | ||||
---|---|---|---|---|
Input signal | 11 | -30 … 120 °C |
| |
1 | 0 … 120 °C |
| ||
2 | 0 … 150 °C |
| ||
3 | 0 … 200 °C |
| ||
Output signal |
| -G1- | Output 0 … 10 V DC, short-circuit proof |
|
-G2- | Output 2 … 10 V DC, short-circuit proof |
| ||
-I1- | Output 0 … 20 mA |
| ||
-I2 | Output 4 … 20 mA |
| ||
VPT5 | __ | -__ | Example: VPT51-I2 |