Measuring transducer for frequency (square wave signal)
Measuring transducers of type VF5 convert frequencies (square wave signals) into standardised output signals. They are mounted on G rails or top-hat rails. The sensor input and supply voltage for the output signal are galvanically isolated. Its compact and robust design, as well as the relevant shipbuilding approvals, make this product ideal for marine applications.
Supply voltage Us | 9...32 VDC |
Input signal | Square wave signals |
Output signal | 0 ... 10 V/DC (VF5..-G1), 2 ... 10 V/DC (VF5..-G2) short-circuit-proof, load current 20 mA max.; 0 ... 20 mA (VF5..-I1), 4 ... 20 mA (VF5..-I2), load resistance 500 Ω max. |
Operating temperature | -20 °C ... +70 °C |
Connection | DIN EN 46244 gold-plated tab connector A6.3 x 0.8 |
Mounting | TS32 G-rail or TS35 top-hat rail |
Type code structure | ||||
---|---|---|---|---|
VF5 | 01 | -I2 | -352 | Example: VF501-I2-352 |
Input range fr / limit frequency fl | ||||
| Output signal | |||
| Limit frequency |
Type code VF5 … | |||||
---|---|---|---|---|---|
Input range fr/ limit frequency fl | 00 | fr: 10 … 100 Hz, fl: 50 … 100 Hz |
| ||
01 | fr: 20 … 1,000 Hz, fl: 100 … 1,000 Hz |
| |||
02 | fr: 200 … 10,000 Hz, fl: 1,000 … 10,000 Hz |
| |||
Output signal |
| -G1- | Output 0 … 10 V DC, short-circuit proof |
| |
-G2- | Output 2 … 10 V DC, short-circuit proof |
| |||
-I1- | Output 0 … 20 mA |
| |||
-I2 | Output 4 … 20 mA |
| |||
Limit frequency |
| -… | Limit frequency in Hz (= 20 mA or 10 V) |
| |
VF5 | __ | -__ | -__ | Example: VF501-I2-352 |